Temperature source
Holds its port at the input temperature (K).
- signal
- thermal
- Modelica Standard Library
- 2 ports
prescribedTemperatureLibraryThermalDescription
Holds its port at the temperature given by an input signal, supplying or absorbing whatever heat flow that takes.
Example
Cooling a hot part A 10 W part cools through a thermal resistance into a heatsink that convects and radiates to 20 °C.
10 WPart 100 J/KHeat flowR 2 K/WHeatsink 500 J/Kh·A 5 W/KConvectionAir 20 °CRadiationRoom 20 °CPart temperatureAcross R350 KHeld at 350 KG 1 W/KBody 100 J/K20 W at 1500 sHeaterBody temperature
Also in this example:ConstantStepHeat capacitorThermal conductorThermal resistorConvectionRadiationFixed temperatureFixed heat flowHeat flow sourceTemperature sensorHeat flow sensorTemperature difference sensor
Ports
Inputs 1
-
T
Temperature to impose, in kelvin.
Conserving terminals 1
-
T
portHeat port held at the input temperature.
Equations
Modelica
port.T = T
Implementation
Modelica Standard Library 4.1.0
MSL documentation Modelica.Thermal.HeatTransfer.Sources.PrescribedTemperatureTips
- The input is in kelvin. Add 273.15 to a Celsius signal.
See also