3-phase transformer (Dy)
Three-phase delta–star transformer with a nominal ratio and winding resistance and stray inductance on each side.
- electrical
- 3-phase
- Modelica Standard Library
- 3 ports
- 5 parameters
threePhaseTransformerLibrary3-phaseDescription
A three-phase two-winding transformer with vector group Dy1: delta-connected high-voltage winding, star-connected low-voltage winding with an accessible neutral. The low-voltage side lags the high-voltage side by 30°.
Each winding has a series resistance and leakage inductance; the core is ideal.
Example
Three-phase transformer A Dy1 transformer with ratio 2 steps 100 V phase voltage down into a star-connected load.
Also in this example:Ground3-phase AC source3-phase resistorStar point3-phase voltage sensor
Ports
Conserving terminals 3
-
HV
plug1High-voltage three-phase plug (phases a, b, c), delta winding. No neutral.
-
LV
plug2Low-voltage three-phase plug (phases a, b, c), star winding.
-
N
starpoint2Neutral of the low-voltage star winding (single-phase pin).
Parameters
-
Voltage ratio HV/LV (line-to-line)
n1≥ 0
Ratio of high-voltage to low-voltage line-to-line voltage. Positive.
-
HV resistance per phase
R10.01 Ω≥ 0
Resistance of each high-voltage winding, in ohms.
-
HV stray inductance per phase
L1sigma0.001 H≥ 0
Leakage inductance of each high-voltage winding, in henries.
-
LV resistance per phase
R20.01 Ω≥ 0
Resistance of each low-voltage winding, in ohms.
-
LV stray inductance per phase
L2sigma0.001 H≥ 0
Leakage inductance of each low-voltage winding, in henries.
Equations
No load: line-to-line voltage of plug1 = n · line-to-line voltage of plug2 Each winding: v = R · i + Lσ · di/dt plus the ideal core coupling, at 20 °C
Implementation
Modelica.Electrical.Machines.BasicMachines.Transformers.Dy.Dy01Assumptions and limitations
- Ideal core: no magnetizing current, core loss, saturation, or inrush.
Tips
- Ground starpoint2 to reference the low-voltage side; the delta side has no ground path of its own.
- At 50 Hz the default 1 mH leakage is about 0.31 Ω per winding, which is large for low-voltage, high-current use; scale it to the rating.
See also