3-phase transformer (Dy)

Three-phase delta–star transformer with a nominal ratio and winding resistance and stray inductance on each side.

  • electrical
  • 3-phase
  • Modelica Standard Library
  • 3 ports
  • 5 parameters
Block3-phase transformer (Dy)KindthreePhaseTransformerLibrary3-phase

Description

A three-phase two-winding transformer with vector group Dy1: delta-connected high-voltage winding, star-connected low-voltage winding with an accessible neutral. The low-voltage side lags the high-voltage side by 30°.

Each winding has a series resistance and leakage inductance; the core is ideal.

Example

Three-phase transformer A Dy1 transformer with ratio 2 steps 100 V phase voltage down into a star-connected load.

100 V 50 HzStar supplyGround supplyStar loadGround loadDy1 transformerGround (neutral)Load 50 ΩOutput voltages
In Gradara, select a 3-phase transformer (Dy) block and press F1, then choose Open example. It opens as a new model in My models, ready to run.

Also in this example:Ground3-phase AC source3-phase resistorStar point3-phase voltage sensor

Ports

Conserving terminals 3

  • HVplug1

    High-voltage three-phase plug (phases a, b, c), delta winding. No neutral.

  • LVplug2

    Low-voltage three-phase plug (phases a, b, c), star winding.

  • Nstarpoint2

    Neutral of the low-voltage star winding (single-phase pin).

Parameters

  • Voltage ratio HV/LV (line-to-line)n1

    ≥ 0

    Ratio of high-voltage to low-voltage line-to-line voltage. Positive.

  • HV resistance per phaseR10.01 Ω

    ≥ 0

    Resistance of each high-voltage winding, in ohms.

  • HV stray inductance per phaseL1sigma0.001 H

    ≥ 0

    Leakage inductance of each high-voltage winding, in henries.

  • LV resistance per phaseR20.01 Ω

    ≥ 0

    Resistance of each low-voltage winding, in ohms.

  • LV stray inductance per phaseL2sigma0.001 H

    ≥ 0

    Leakage inductance of each low-voltage winding, in henries.

Equations

Modelica
No load: line-to-line voltage of plug1 = n · line-to-line voltage of plug2
Each winding: v = R · i + Lσ · di/dt plus the ideal core coupling, at 20 °C

Implementation

Modelica Standard Library 4.1.0Modelica.Electrical.Machines.BasicMachines.Transformers.Dy.Dy01
MSL documentation

Assumptions and limitations

  • Ideal core: no magnetizing current, core loss, saturation, or inrush.

Tips

  • Ground starpoint2 to reference the low-voltage side; the delta side has no ground path of its own.
  • At 50 Hz the default 1 mH leakage is about 0.31 Ω per winding, which is large for low-voltage, high-current use; scale it to the rating.